Magnetic Valve Control - Specification
Input :
Pin connection for Remote Control :
| 25 poles (SUB-D-female) | CON-7 | . |
| Pin : | Function : | In / Out |
| 1 | Remote control of magnetic valve 1, On/Out (0) Off/In (1) | in |
| 2 | Remote control of magnetic valve 3, On/Out (0) Off/In (1) | in |
| 3 | Remote control of magnetic valve 5, On/Out (0) Off/In (1) | in |
| 4 | Tells position of the manual switch, Manual (1) / Remote (0) | out |
| 5 | GND | out |
| 6 | Status from magnetic valve 2, pin 4, '0' for OUT (on) | out |
| 7 | Status from magnetic valve 4, pin 4, '0' for OUT (on) | out |
| 8 | Status from magnetic valve 6, pin 4, '0' for OUT (on) | out |
| 9 | Status from magnetic valve 2, pin 3, '0' for IN (off) | out |
| 10 | Status from magnetic valve 4, pin 3, '0' for IN (off) | out |
| 11 | Status from magnetic valve 6, pin 3, '0' for IN (off) | out |
| 12 | nc. | . |
| 13 | nc. | . |
| 14 | Remote control of magnetic valve 2, On/Out (0) Off/In (1) | in |
| 15 | Remote control of magnetic valve 4, On/Out (0) Off/In (1) | in |
| 16 | Remote control of magnetic valve 6, On/Out (0) Off/In (1) | in |
| 17 | Vcc +5V | out |
| 18 | Status from magnetic valve 1, pin 4, '0' for OUT (on) | out |
| 19 | Status from magnetic valve 3, pin 4, '0' for OUT (on) | .out |
| 20 | Status from magnetic valve 5, pin 4, '0' for OUT (on) | out |
| 21 | Status from magnetic valve 1, pin 3, '0' for IN (off) | out |
| 22 | Status from magnetic valve 3, pin 3, '0' for IN (off) | out |
| 23 | Status from magnetic valve 5, pin 3, '0' for IN (off) | out |
| 24 | Vcc +5V | out |
| 25 | GND | out |
Status output is pulled up with a 1K resistor to +5V
The remote control inputs is pulled up with a 10K resistor to +5V
The manual (1) / remote (0) output is pulled up with a 178R resistor and a LED in series to +5V
Output :
Pin connection for the Magetic Valve :
| 8 poles (BURNDY-female) | CON-1 to CON-6 | . |
| Pin : | Function : | In / Out |
| 1 | GND | . |
| 2 | +24V (With Fuse) | out |
| 3 | Status, '0' for IN (off) | in |
| 4 | Status, '0' for OUT (on) | in |
| 5 | Control of valve, On/Out (0V) Off/In (open) | out |
| 6 | nc. | . |
| 7 | nc. | . |
| 8 | nc. | . |
Status input is pulled up with a 1K resistor to +5V
The maximum current pin 5 can pull down is 250 mA
Last Modified 11 January 2019